DocumentCode :
3754372
Title :
Graphical analysis method to identify power -balanced grid areas for intended islanding operation
Author :
F. Grumm;M. Plenz;G. Kaatz;D. Schulz;K. Lehmann
Author_Institution :
Helmut Schmidt University / University of the Federal Armed Forces Hamburg, Germany
fYear :
2015
Firstpage :
901
Lastpage :
906
Abstract :
The increasing number of decentralized power generators in the low-voltage and medium-voltage grid induce multiple short-time power- balanced areas. These areas intensify the problem to determine the dynamic energy flow of the distribution grid. The identification of power- balanced grid parts is a time consuming and computationally intensive process. Hence, this contribution presents a simplified identification method that has minor computational effort. The method computes a simplified energy flow over more than one voltage level. So, it is even possible to identify power- balanced grid parts that are spread over different voltage levels. For evaluation and validation the method is compared to a traditional grid simulation with DIgSILENT PowerFactory.
Keywords :
"Biomass","Photovoltaic systems","Chlorine"
Publisher :
ieee
Conference_Titel :
Renewable Energy Research and Applications (ICRERA), 2015 International Conference on
Type :
conf
DOI :
10.1109/ICRERA.2015.7418540
Filename :
7418540