• DocumentCode
    3760256
  • Title

    Anti-saturation algorithm in differential protection based on the phaselet

  • Author

    Zhiguo Hao;Jun Guan;Wenzhe Chen;Dai Feng;Deng Jieqing;Liu Yidan;Jia Xiaohui

  • Author_Institution
    School of Electric Engineering, Xi´an Jiaotong University, Xi´an, China
  • fYear
    2015
  • Firstpage
    1030
  • Lastpage
    1035
  • Abstract
    Current-transformer (CT) is prone to get into transient saturated during the fault in the power system. The transient saturation of CTs will cause serious distortion in the secondary side, operation performance of differential protection based on the traditional algorithm is seriously influenced. The phaselet algorithm can accurately obtain the basic frequency component of the fault current with the unsaturated data segment of CTs´ distorted secondary current in a relatively short time window. This paper researches the principle and features of the phaselet algorithm, eliminates the influence of the decaying DC component with the first order difference compensation, gives out the calculation process of the phaselet algorithm, proposes the scheme for the CT´s anti-saturation of the differential protection based on the phaselet algorithm. Finally, the accuracy of the phaselet algorithm is verified by CTs´ transient experiment data, and the validity of the scheme applying in the line differential protection is tested by the simulation in PACAD.
  • Keywords
    "Decision support systems","Harmonic analysis","Current transformers","Transient analysis","Power industry"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432382
  • Filename
    7432382