• DocumentCode
    3760266
  • Title

    Analysis on the effects of 500kV main transformer single-phase replacement on differential protection

  • Author

    Meng Li;Chengjun Xia;Guihua Qiu

  • Author_Institution
    School of Electric Power, South China University of Technology, SCUT Guangzhou, China
  • fYear
    2015
  • Firstpage
    1085
  • Lastpage
    1088
  • Abstract
    Combined with the project which studies the feasibility of replacing a 500kV substation No.2 main transformer and based on PSCAD/EMTDC, this paper introduces a special auto-transformer model to study the effects of percentages of three-phase winding short circuit voltage on the transformer differential protection under normal operation and fault conditions after replacing the B-phase transformer for No.2 main transformer with original A-phase transformer for No.1 main transformer. It is preliminarily concluded that the replacement has little effect on differential protection and a certain degree of asymmetry of the percentage of three-phase winding short circuit voltage is allowed, which provides new ideas and references for further study on three-phase transformer single-phase replacement.
  • Keywords
    "Analytical models","Grounding","Harmonic analysis","Windings","Power industry","Substations","Integrated circuit modeling"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432392
  • Filename
    7432392