Identification method for internal and external faults based on amplitude feature of backward traveling wave for HVDC transmission line
Author
Xiaopeng Li;Sheng Lin;Shuai Jiang
Author_Institution
State Grid Sichuan Electric Power Research Institute, Chengdu, Sichuan Province, China
fYear
2015
Firstpage
1166
Lastpage
1169
Abstract
The theoretical analyses about the traveling wave transmission process for internal and external faults at HVDC transmission lines show that, in a short time, for internal faults, the backward traveling waves can be detected at both line terminals. For external faults, the backward traveling wave can be detected only at one line terminal. The backward traveling wave in the other terminal is zero in theory. Taking the calculation error and noise into account, the amplitude of the backward traveling wave is still very small. Thus, the identification method for internal and external faults for HVDC lines can be proposed by com paring the amplitude of the backward traveling waves at both ends of line. For internal faults, the ratio of the integral results is relatively small. However, for external faults, the ratio of the integral results is relatively large. Plenty of simulation results based on PSCAD/EMTDC indicate that the proposed protection method can discriminate internal faults from external faults under various fault conditions including faults with high fault resistances.
Keywords
"Rectifiers","Inverters","HVDC transmission","Fault diagnosis","Power industry","Simulation","Power transmission lines"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432410
Filename
7432410
Link To Document