• DocumentCode
    3760284
  • Title

    Identification method for internal and external faults based on amplitude feature of backward traveling wave for HVDC transmission line

  • Author

    Xiaopeng Li;Sheng Lin;Shuai Jiang

  • Author_Institution
    State Grid Sichuan Electric Power Research Institute, Chengdu, Sichuan Province, China
  • fYear
    2015
  • Firstpage
    1166
  • Lastpage
    1169
  • Abstract
    The theoretical analyses about the traveling wave transmission process for internal and external faults at HVDC transmission lines show that, in a short time, for internal faults, the backward traveling waves can be detected at both line terminals. For external faults, the backward traveling wave can be detected only at one line terminal. The backward traveling wave in the other terminal is zero in theory. Taking the calculation error and noise into account, the amplitude of the backward traveling wave is still very small. Thus, the identification method for internal and external faults for HVDC lines can be proposed by com paring the amplitude of the backward traveling waves at both ends of line. For internal faults, the ratio of the integral results is relatively small. However, for external faults, the ratio of the integral results is relatively large. Plenty of simulation results based on PSCAD/EMTDC indicate that the proposed protection method can discriminate internal faults from external faults under various fault conditions including faults with high fault resistances.
  • Keywords
    "Rectifiers","Inverters","HVDC transmission","Fault diagnosis","Power industry","Simulation","Power transmission lines"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432410
  • Filename
    7432410