• DocumentCode
    3760373
  • Title

    Fault analysis and structure optimization of 40.5kV wall bushing

  • Author

    Fucheng Lang;Hongkui Zhang

  • Author_Institution
    Electric Power Research Institute of State Grid Liaoning, Electric Power Co., Ltd., High Voltage and Large Current Laboratory of State Grid Corporation, Shenyang, Liaoning, 110006, China
  • fYear
    2015
  • Firstpage
    1628
  • Lastpage
    1631
  • Abstract
    Based on the explosion fault of wall bushing used in a 35kV substation, analyzing operation environment, appearance inspection of bushing and electrical test on other bushings operating well, the key causes which lead to this failure were found: design defects and high non-uniform electrical field distribution, simultaneously, heavy operation condition and high humidity are the exterior factors resulting in the explosion fault. For improving the electrical performance of bushing and electrical field distribution, the new design with shield ring was presented. At the same time, improvement solutions, adding the heater and fan in busbar compartment, used to reducing the humidity inside busbar compartment of switchgear were presented in this paper. After these improvement measures were carried out, the switchgears operate very well in safe condition.
  • Keywords
    "Insulators","Partial discharges","Explosions","Inspection","Humidity","Switchgear","Electric fields"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432503
  • Filename
    7432503