DocumentCode
3760401
Title
Evaluation of the calculation method for stray losses in structural parts of HVDC converter transformers
Author
Yaqing Liu;Dandan Zhang;Zhenbiao Li;Qinqing Huang;Menghu Li;Bin Li;Jian Liu
Author_Institution
State Key Laboratory of Advanced Electromagnetic Engineering and Technology, Huazhong University of Science and Technology, Wuhan 430074, China
fYear
2015
Firstpage
1780
Lastpage
1785
Abstract
Stray losses in structural parts are calculated separately during determining load losses of HVDC converter transformers, but the calculation method proposed by IEC 61378-2 standard shows significant difference from the experimental results. The nonlinearity, hysteresis losses, and frequency characteristic are thought as the sources of errors in this paper, and then an electromagnetic-circuit coupling FEM analysis is performed to investigate them. It is shown that the frequency characteristic of the stray losses is the major factor that causes the errors, and the material characteristic should be considered. The magnetic and nonmagnetic materials are suggested to be calculated separately.
Keywords
"Magnetic hysteresis","Decision support systems","IEC Standards","Finite element analysis","Analytical models","Power industry","HVDC transmission"
Publisher
ieee
Conference_Titel
Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
Type
conf
DOI
10.1109/DRPT.2015.7432531
Filename
7432531
Link To Document