• DocumentCode
    3760411
  • Title

    Research on impacts of UHVDC transmission on operating stabilities of receiving-end power grid

  • Author

    Peng Wei;Jiankun Liu;Qian Zhou;Chenggen Wang

  • Author_Institution
    Jiangsu Electric Power Research Institute, Nanjing 211103, China
  • fYear
    2015
  • Firstpage
    1827
  • Lastpage
    1829
  • Abstract
    Research on interaction impacts on UHVDC after fault in receiving-end power grid is important for improving stability. In order to research the running stability of the receiving end grid under typical fault take Jinsu UHVDC project as back ground, the sending grid and also the entire main grid of Jiangsu outside Jinsu UHVDC were established base on ADPSS. In accordance with the actual project DC line, filters, converter transformer and other DC electromagnetic transient model. The influence of typical faults on the receiving end grid such as AC bus fault, three-phase short circuit on line and bipolar locking were analyzed. Finally, restart procedure of bipolar locking were studied. Simulation results shows that serious fault may lead to DC bipolar locking, bipolar blocking or typical fault in AC system; Jiangsu power grid can restart smoothly after bipolar blocking, but the receiving end power grid can keep stable operation after bipolar locking.
  • Keywords
    "Circuit faults","Power grids","Radio frequency","Circuit stability","Power system stability","Stability analysis","Inverters"
  • Publisher
    ieee
  • Conference_Titel
    Electric Utility Deregulation and Restructuring and Power Technologies (DRPT), 2015 5th International Conference on
  • Type

    conf

  • DOI
    10.1109/DRPT.2015.7432541
  • Filename
    7432541