• DocumentCode
    3762684
  • Title

    Assessment of TRV parameters and overvoltages in three-phase ungrounded faults

  • Author

    Alejandro Marmolejo;Mirko Palazzo

  • Author_Institution
    ABB Switzerland Ltd., Zurich, Switzerland
  • fYear
    2015
  • Firstpage
    321
  • Lastpage
    326
  • Abstract
    The transient recovery voltage requirements laid down in IEC/IEEE 62271-37-013 for testing generator circuit-breakers are determined for the first-pole-to-clear in case of a three-phase grounded fault despite it is recognized that the rate-of-rise in such case is somewhat smaller and therefore less severe than the rate-of-rise in case of ungrounded faults. The occurrence of a three-phase ungrounded fault in power stations is rare but cannot be completely ruled out. Such fault may arise, for example, inside the panel of MV-switchgear with non-segregated busducts or when active arc mitigation devices which transform an arc fault into a three-phase ungrounded bolted short-circuit are employed. The transient recovery voltage requirements for three-phase ungrounded faults are assessed in the present work. Also the voltage transients occurring at the fault location and generator neutral are investigated.
  • Keywords
    "Surges","Capacitance"
  • Publisher
    ieee
  • Conference_Titel
    Information Technology, Computer, and Electrical Engineering (ICITACEE), 2015 2nd International Conference on
  • Print_ISBN
    978-1-4799-9861-6
  • Type

    conf

  • DOI
    10.1109/ICITACEE.2015.7437822
  • Filename
    7437822