• DocumentCode
    376318
  • Title

    Steady-state performance of a grid interactive voltage source inverter

  • Author

    Ashari, M. ; Nayar, Chem V. ; Islam, Syed

  • Author_Institution
    Dept. of Electr. Engr., Inst. of Technol. Sepuluh Nopember, Surabaya, Indonesia
  • Volume
    1
  • fYear
    2001
  • fDate
    15-19 July 2001
  • Firstpage
    650
  • Abstract
    This paper presents the steady-state performance of a grid interactive voltage source inverter (VSI). The inverter is synchronized and connected to the grid through a link inductor performing an "in-line" uninterruptible power supply with load voltage stabilization. A chart showing the active-reactive (PQ) power flow between the inverter and grid has been developed. The chart is used to compute the link inductor value, so the system can operate in the specified grid voltage and input power factor range. Results from laboratory tests using a 15 kVA, 120 volts DC to 230 volts AC are also included.
  • Keywords
    inductors; invertors; load flow; power factor; uninterruptible power supplies; 120 V; 15 kVA; 230 V; active-reactive power flow; battery storage; grid interactive voltage source inverter; in-line uninterruptible power supply; input power factor; laboratory tests; link inductor; steady-state performance; voltage-controlled inverter; Grid computing; Inductors; Inverters; Laboratories; Load flow; Reactive power; Steady-state; Testing; Uninterruptible power systems; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Summer Meeting, 2001
  • Conference_Location
    Vancouver, BC, Canada
  • Print_ISBN
    0-7803-7173-9
  • Type

    conf

  • DOI
    10.1109/PESS.2001.970115
  • Filename
    970115