DocumentCode
376330
Title
Brazilian defense plan against extreme contingencies
Author
Filho, V.X. ; Pilotto, L.A.S. ; Martins, N. ; Carvalho, A.R.C. ; Bianco, A.
Author_Institution
Centro de Pesquisas de Energia Eletrica, CEPEL, Rio de Janeiro, Brazil
Volume
2
fYear
2001
fDate
15-19 July 2001
Firstpage
834
Abstract
This paper presents some of the short-term measures developed from the studies following the blackout in the Brazilian South/Southeast/Center-West power system in March 11/sup th/ 1999. The concept of security zones and network security matrix is introduced. A new PLC-based SPS was designed to create controllability zones. This new scheme was named security control and is triggered by network topological changes. The security control is fast acting, with clearing times around 200 ms. A typical security controller logic is presented, showing its benefits for the Brazilian interconnected power system.
Keywords
controllability; power system interconnection; power system protection; power system security; power system stability; programmable controllers; Brazilian South/Southeast/Center-West power system; Brazilian interconnected power system; angle stability control; blackout; clearing times; controllability zones; network security matrix; programmable logic controller; security controller logic; security zones; short-term measures; voltage collapse; Control systems; Power generation; Power system interconnection; Power system measurements; Power system protection; Power system reliability; Power system security; Power system stability; Senior members; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Summer Meeting, 2001
Conference_Location
Vancouver, BC, Canada
Print_ISBN
0-7803-7173-9
Type
conf
DOI
10.1109/PESS.2001.970160
Filename
970160
Link To Document