DocumentCode
3765226
Title
High-efficiency improved 12kW switched mode telecom rectifier
Author
P Saravana Prakash;R. Kalpana;Bhim Singh;G. Bhuvaneswari
Author_Institution
Department of E & E, NITK, Surathkal, Mangalore, India
fYear
2015
Firstpage
382
Lastpage
386
Abstract
In this paper an improved switched mode telecom rectifier for a 12kW telecommunication system is presented. An improved telecom rectifier is a combination of phase-shift transformer based ac-dc converter and passive high pass filter. The phase-shift transformer and high pass filter is realized with a fractional magnetic rating of the load. The supply current is almost sinusoidal with low total harmonic distortion, and the power factor (PF) is close to unity. The complete design of phase-shift transformer based ac-dc converter and passive high pass filter is presented in this paper. The 12kW telecom rectifier is designed, modeled and simulated to reduce the total harmonic distortion (THD) of the input ac mains current and to improve the power factor. A laboratory prototype of phase-shift transformer based ac-dc converter is developed and the results are presented to validate the design topology.
Keywords
"Passive filters","Power harmonic filters","Rectifiers","Windings","Switches","Reactive power"
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering (WIECON-ECE), 2015 IEEE International WIE Conference on
Type
conf
DOI
10.1109/WIECON-ECE.2015.7443945
Filename
7443945
Link To Document