Symmetrical components based advanced scheme for detection of incipient inter-turn fault in transformer
Author
P. A. Venikar;Makarand S. Ballal;B. S. Umre;H. M. Suryawanshi
Author_Institution
Department of Electrical Engineering, Visvesvaraya National Institute of Technology, Nagpur, India 440010
fYear
2015
Firstpage
127
Lastpage
132
Abstract
Phase current based transformer differential protection is commonly used for detection of inter-turn fault. Initial pick-up and commonly used dual slope characteristics provides security against spill current due to on-load tap changer (OLTC) operation and CT saturation because of through fault. However, this limits ability to detect presence of inter-turn fault at an incipient stage. This paper presents a novel approach based on use of negative sequence components for incipient inter-turn fault detection. This technique offers higher sensitivity as compared with conventional phase based protection scheme. A comparison with conventional scheme with commonly used settings is presented for unbalanced load, over-voltage and under-voltage conditions. Experimental results indicate that the proposed scheme is able to detect fault involving 3% turns and fault current of 1 p.u.
Keywords
"Circuit faults","Fault detection","Fault currents","Impedance","Algorithm design and analysis","IP networks","Relays"