DocumentCode :
3767110
Title :
Detection of partial discharges and its effect on solid insulation used in high voltage cable
Author :
Subrata Karmakar;Soumya Mishra
Author_Institution :
Department of Electrical Engineering, National Institute of Technology, Rourkela-769008, Odisha, India
fYear :
2015
Firstpage :
204
Lastpage :
208
Abstract :
Most of the high voltage (HV) power equipment is made up with solid insulation like paper insulation, glass insulation, epoxy insulation etc. The oldest kind of insulating material among all insulation, the paper insulation is used in cable and nowadays the Cross linked Polyethylene (XLPE) is commonly used for cable insulation. The presence of impurities in the insulation system is one of the root causes of insulation failure as they are form a weak zone inside the healthy insulation system. Therefore, early identification of degradation process like formation of electrical tree structures inside such solid electrical insulation due to high voltage tress during its operating life is utmost requirement to prevent the electrical power equipment from a sudden and complete insulation failure. To study the growth mechanism of electrical tree structure inside the insulation with different applied high voltage a commonly used insulating material like XLPE insulation in HV power cable are consider for this present work. This work also describes the ageing process by conducting the partial discharge (PD) test on the same insulating materials. Finally, the effect of PD on insulation i.e., formation of electrical tree structure on solid insulation was observed by using Scanning Electron Microscope (SEM) and analyzed.
Keywords :
"Partial discharges","Power cables","Electrodes","Power cable insulation","Needles"
Publisher :
ieee
Conference_Titel :
Condition Assessment Techniques in Electrical Systems (CATCON), 2015 International Conference on
Type :
conf
DOI :
10.1109/CATCON.2015.7449535
Filename :
7449535