• DocumentCode
    3767917
  • Title

    Improvement in dynamic stability of self-excited induction generator with short-shunt capacitors

  • Author

    Xin Zhen Wu;Yang Zhang;Kai Wang

  • Author_Institution
    Department of Electrical Engineering, Qingdao University, Qingdao 266071, China
  • fYear
    2015
  • Firstpage
    116
  • Lastpage
    117
  • Abstract
    Short-shunt connection of capacitors is proposed to improve the dynamic stability of the self-excited induction generator (SEIG). The transient model is deduced according to the equivalent circuits of the generator under αβ0 stationary reference frames. The state equations of the circuits are linearized locally and then solved by Runge-Kutta method. The improved eigenvalue method is utilized to study transient process of the induction generator under various loading conditions. The analyzed results show that the short-shunt compensation capacitor can efficiently enhance the loading capacity of induction generators. The agreements between calculated results and experimental results verify the developed method.
  • Keywords
    "Eigenvalues and eigenfunctions","Transient analysis","Capacitors","Mathematical model","Stability analysis","Induction generators"
  • Publisher
    ieee
  • Conference_Titel
    Applied Superconductivity and Electromagnetic Devices (ASEMD), 2015 IEEE International Conference on
  • Print_ISBN
    978-1-4673-8106-2
  • Type

    conf

  • DOI
    10.1109/ASEMD.2015.7453493
  • Filename