DocumentCode
3768128
Title
Research of the loss of the corrugated stainless steel pipe in HTS cable
Author
Xi Ze Zhang;Xi Hua Zong;Yun Wu Han;Xiang Tian;Xiao Hong Lu;Zhi Guang Yu
Author_Institution
Superconducting Project Technologies Research Centre, Shanghai Electric Cable Research Institute, Shanghai 200093, China
fYear
2015
Firstpage
576
Lastpage
577
Abstract
Stainless steel is usually non-magnetic or low magnetic austenitic stainless steel, which may convert to martensite when mechanical deformed. The stainless steel corrugated pipe becomes magnetic when marttensite exist, which cause hysteresis loss happens when AC current pass through the cable inside the corrugated pipe. In this paper, the hysteresis loss of the corrugated pipe was tested, and the metallographic and hysteresis loop of the steel was learned.
Keywords
"Magnetic hysteresis","Superconducting cables","Steel","Power cables","High-temperature superconductors","Cable shielding","Cable insulation"
Publisher
ieee
Conference_Titel
Applied Superconductivity and Electromagnetic Devices (ASEMD), 2015 IEEE International Conference on
Print_ISBN
978-1-4673-8106-2
Type
conf
DOI
10.1109/ASEMD.2015.7453711
Filename
7453711
Link To Document