Corona discharges in d-c and partially rectified a-c insulation systems
Author
Thomas W. Dakin
Author_Institution
Westinghouse Research Laboratories, Pittsburgh, Pennsylvania
fYear
1968
Firstpage
82
Lastpage
84
Abstract
During the past several decades of rather intensive study of corona (partial) discharges and their effects on insulation systems, most of the attention has been focused on a-c discharge behavior. This has been rightly motivated by the much more serious effects of corona in most a-c insulation applications, where usually many more discharges can occur, during an average time, than with d-c. Because discharges in d-c insulation systems are much more intermittent, their rate of erosion or penetration of insulation barriers is correspondingly reduced, and it has been practical to apply much higher d-c stresses, without completely preventing corona, than with a-c cases. This characteristic of d-c stresses has been utilized effectiyely in d-c over-voltage testing of insulation systems, particularly of rotating machines.