• DocumentCode
    3769738
  • Title

    Corona discharges in d-c and partially rectified a-c insulation systems

  • Author

    Thomas W. Dakin

  • Author_Institution
    Westinghouse Research Laboratories, Pittsburgh, Pennsylvania
  • fYear
    1968
  • Firstpage
    82
  • Lastpage
    84
  • Abstract
    During the past several decades of rather intensive study of corona (partial) discharges and their effects on insulation systems, most of the attention has been focused on a-c discharge behavior. This has been rightly motivated by the much more serious effects of corona in most a-c insulation applications, where usually many more discharges can occur, during an average time, than with d-c. Because discharges in d-c insulation systems are much more intermittent, their rate of erosion or penetration of insulation barriers is correspondingly reduced, and it has been practical to apply much higher d-c stresses, without completely preventing corona, than with a-c cases. This characteristic of d-c stresses has been utilized effectiyely in d-c over-voltage testing of insulation systems, particularly of rotating machines.
  • Keywords
    "Corona","Discharges (electric)","Threshold voltage","Insulation","Surface discharges","Stress","Voltage control"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference, 1968 8th
  • Print_ISBN
    978-1-5090-3107-8
  • Type

    conf

  • DOI
    10.1109/EIC.1968.7456109
  • Filename
    7456109