    The measurement of moisture concentration in cable insulation

  • Author

    Charles Wade;Laura DiBenedetto;Julian F. Johnson;Dwight H. Damon

  • Author_Institution
    The Electrical Insulation Research Center, The Institute of Materials Science, The University of Connecticut, Storrs, 06268, United States
  • fYear
    1985
  • Firstpage
    52
  • Lastpage
    55
  • Abstract
    The results of measurement of the moisture content of XLPE cable insulation obtained from a DuPont model 903 Moisture Evolution Analyzer often disagrees with the results of the same measurements made with a Mitsubishi Moisture Meter by as much as a factor of two. The former instrument uses a cell containing P2O5 as its active element, and the latter performs an automated Karl Fisher titration. The two instruments were calibrated using the water hydration of sodium tartrate as a standard. Moisture measurements made as a function of the oven temperature for both instruments were in good agreement with weight loss measurements made by thermogravimetric analysis of the sodium tartrate. These results and others have shown that the accuracy and precision of both instruments are within ± 1% for the measurement of amounts of water of the order of 1000 micrograms. The present results show that the lack of agreement among the measurements can be explained as the result of interference by such volatile substances as acetophenone and cumyl alcohol.
  • Keywords
    "Moisture","Instruments","Sodium","Moisture measurement","Cable insulation","Standards","Temperature measurement"
  • Publisher
    ieee
  • Conference_Titel
    Electrical/Electronics Insulation Conference, 1985 EIC 17th
  • Print_ISBN
    978-1-5090-3115-3
  • Type

    conf

  • DOI
    10.1109/EIC.1985.7458579
  • Filename
    7458579