• DocumentCode
    3771533
  • Title

    Techniques for the thermal evaluation of transformer insulation systems

  • Author

    G. I. Duncan

  • Author_Institution
    Insulating Materials Engineer, Specialty Transformer Department, General Electric Company, Fort Wayne, Indiana
  • fYear
    1963
  • Firstpage
    235
  • Lastpage
    249
  • Abstract
    A unique test method for screening transformer insulation systems was presented in a paper (1) during the 1962 Electrical Insulation Conference. This test method referred to as "Progressive Temperature Testing" was based on increasing the test temperature in finite steps until the insulation system fails. The test temperatures and times were selected in accordance with the Arrhenius(2) relationship of the logarithm of life and the reciprocal of absolute temperature.
  • Keywords
    "Temperature distribution","Aging","Insulation","Power transformer insulation","Correlation","Lifting equipment"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference Materials and Application, 1963 EI
  • Print_ISBN
    978-1-5090-3104-7
  • Type

    conf

  • DOI
    10.1109/EIC.1963.7461799
  • Filename