DocumentCode :
3772549
Title :
Electrode surface effects on large gap breakdown in SF6 gas
Author :
C. M. Cooke
Author_Institution :
Massachusetts Institute of Technology, High Voltage Research Laboratory, United States
fYear :
1982
fDate :
6/1/1982 12:00:00 AM
Firstpage :
215
Lastpage :
215
Abstract :
An Investigation of electrode surface effects has indicated that surface defects are a major cause of non-ideal performance of large gaps used in SF6 gas. A discharge inception model with a sensitivity analysis demonstrates that realistic size surface irregularities can initiate failures that compare well with test measurements. Also, a method to treat area effects by using surface statistics has been demonstrated.
Keywords :
"Surface treatment","Electrodes","Sulfur hexafluoride","Voltage measurement","Electric breakdown","Breakdown voltage","Size measurement"