Title :
Accuracy of current transformer with current errors at harmonics equal to the limiting values defined in IEC 60044-8 standard for transformation of distorted primary current
Author :
Michal Kaczmarek
Author_Institution :
Institute of Electrical Power Engineering, Lodz University of Technology, Lodz, Poland
fDate :
7/1/2015 12:00:00 AM
Abstract :
Accuracy requirements at harmonics are defined for electronic current transformers in IEC 60044-8 standard. As indicated there defined limiting values of current error ensure that the contribution of harmonics measurement error would add roughly 15%, in the worst case, on the theoretical error of the corresponding power metering class accuracy. In accordance with IEC 61000-3-12 standard total harmonic distortion of current caused by emission of higher harmonics from equipment connected to public low-voltage systems may be equal to 47%. Accuracy of 0.1-1 classes measuring current transformers with current errors at harmonics equal to the limiting values defined in IEC 60044-8 standard for transformation of such a distorted primary current may decrease over 12 times in relation to accuracy designated for transformation of sinusoidal current of frequency 50 Hz for which they were designed.
Keywords :
"Harmonic analysis","Power system harmonics","Harmonic distortion","Limiting","IEC Standards","Current transformers"
Conference_Titel :
Modern Electric Power Systems (MEPS), 2015
DOI :
10.1109/MEPS.2015.7477205