DocumentCode :
3782644
Title :
Acoustic partial discharge measurements for transformer insulation-an experimental validation
Author :
S. Rengarajan;A. Bhoomaial;K. Krishna Kishore
Author_Institution :
High Voltage Lab., Bharat Heavy Electr. Ltd., Hyderabad, India
Volume :
5
fYear :
1999
fDate :
6/21/1905 12:00:00 AM
Firstpage :
288
Abstract :
Acoustic partial discharge (PD) measurement is a useful method of identifying and locating PD in a power transformer in service. In this paper an experimental validation has been performed on a transformer insulation model using an acoustic PD detector. While the efficacy of the method is proved, it is observed that the signal gets attenuated significantly when it passes through pressboard barriers. Even though acoustic PD values can be correlated with the maximum discharge magnitude for a single discharge activity in the laboratory simulations, this relationship could not be established during actual PD measurements in a transformer at site, as the acoustic PD signal depends upon many factors.
Publisher :
iet
Conference_Titel :
High Voltage Engineering, 1999. Eleventh International Symposium on (Conf. Publ. No. 467)
ISSN :
0537-9989
Print_ISBN :
0-85296-719-5
Type :
conf
DOI :
10.1049/cp:19990942
Filename :
818294
Link To Document :
بازگشت