DocumentCode :
3783932
Title :
Detection of water trees in medium voltage cables by RVM, without reference measurements
Author :
B. Alijagic-Jonuz;P.H.F. Morshuis;H.J. van Breen;J.J. Smit
Author_Institution :
Delft Univ. of Technol., Netherlands
fYear :
2001
fDate :
6/23/1905 12:00:00 AM
Firstpage :
504
Lastpage :
507
Abstract :
Measurement of the polarization spectrum by Recovery Voltage Measurement (RVM) is one among several methods, which are proposed in the literature to characterize the state of deterioration of water-treed cable insulation. It has previously been shown that it is possible to use RVM for detection of water trees in PE and XLPE cables. In this paper the authors present a methodology that allows the detection of water trees at low DC test voltage without the need for a reference measurement. This methodology makes use of a so called division spectrum, which is obtained from the results of two separate recordings of the polarization spectrum.
Keywords :
"Trees - insulation","Medium voltage","Polarization","Testing","Power transformer insulation","Cable insulation","Electrical resistance measurement","Voltage measurement","Aging","Low voltage"
Publisher :
ieee
Conference_Titel :
Solid Dielectrics, 2001. ICSD ´01. Proceedings of the 2001 IEEE 7th International Conference on
Print_ISBN :
0-7803-6352-3
Type :
conf
DOI :
10.1109/ICSD.2001.955709
Filename :
955709
Link To Document :
بازگشت