DocumentCode :
3795700
Title :
Influence of switching operations on the vacuum interrupter dielectric strength
Author :
P. Osmokrovic
Author_Institution :
Fac. of Electr. Eng., Belgrade Univ., Yugoslavia
Volume :
8
Issue :
1
fYear :
1993
Firstpage :
175
Lastpage :
181
Abstract :
The influence of switching operations on dielectric strength of vacuum interrupters is described. Detailed experimental procedure and numerical processing of experimental results are presented. The breakdown voltage and emission current before and after switching operations were experimentally determined for closing without current/breaking without current, closing without current/breaking with rated current, and closing without current/breaking of rated short-circuit current. The interconnect gap was varied, and DC lightning impulse voltage (1.2/50 mu s) and AC 50 Hz voltages were applied. Three types of commercially available vacuum interrupter were tested, two with transverse and one with axial magnetic field and all having CuCr contacts. It was found which physical mechanisms determine the influence of switching operations.
Keywords :
"Interrupters","Dielectric breakdown","Contacts","Surface topography","Testing","Surface discharges","Voltage","Magnetic fields","Electrodes","Dielectrics and electrical insulation"
Journal_Title :
IEEE Transactions on Power Delivery
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.180334
Filename :
180334
Link To Document :
بازگشت