DocumentCode
3795715
Title
Computation of current transformer transient performance
Author
M. Poljak;N. Kolibas
Author_Institution
Rade Koncar Co., Zagreb, Yugoslavia
Volume
3
Issue
4
fYear
1988
Firstpage
1816
Lastpage
1822
Abstract
A computer program for the calculation of the transient performance of a current transformer during short-circuit conditions is discussed. A numerical analysis that includes the dynamic hysteresis loops is used to calculate the performance, and results are compared with those of direct laboratory tests. The test methods, proposed in IEC Document 38 (Central Office) 78, are discussed. Results show the calculation can successfully replace expensive laboratory tests.
Keywords
"Current transformers","Magnetic hysteresis","Testing","Magnetic cores","Protection","Transformer cores","Laboratories","IEC standards","Physics computing","Saturation magnetization"
Journal_Title
IEEE Transactions on Power Delivery
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.193988