• DocumentCode
    3795849
  • Title

    Experimental evaluation of EMTP-based current transformer models for protective relay transient study

  • Author

    M. Kezunovic;L. Kojovic;A. Abur;C.W. Fromen;D.R. Sevcik;F. Phillips

  • Author_Institution
    Texas A&M Univ., TX, USA
  • Volume
    9
  • Issue
    1
  • fYear
    1994
  • Firstpage
    405
  • Lastpage
    413
  • Abstract
    This paper describes an EPRI study of current transformer (CT) digital models intended for protective relay transient performance analysis. Experimental evaluation of CT models implemented using the Electromagnetic Transient Program (EMTP) was carried out. Two relaying CTs with 600/5 and 2000/5 ratios were used in the study. Experiments in a high power laboratory were performed to obtain transient responses. Simulation of the CT response to the same transient events was set up using three different CT models. They were implemented based on the saturable transformer and nonlinear reactor models available in an EMTP. Comparison of laboratory and simulation results indicates that CT models developed based on the EMTP program give satisfactory results for most of the cases. It has also been discovered that in some instances EMTP models need further improvements.
  • Keywords
    "Current transformers","EMTP","Electromagnetic transients","Digital relays","Protective relaying","Laboratories","Protection","Transient analysis","Performance analysis","Electromagnetic modeling"
  • Journal_Title
    IEEE Transactions on Power Delivery
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.277712
  • Filename