DocumentCode :
3796113
Title :
Transformer tap position estimation and bad data detection using dynamic signal modelling
Author :
E. Handschin;E. Kliokys
Author_Institution :
Dept. of Electr. Eng., Dortmund Univ., Germany
Volume :
10
Issue :
2
fYear :
1995
Firstpage :
810
Lastpage :
817
Abstract :
Tracking estimation of a transformer tap position is considered. An estimation algorithm incorporating additional information about the dynamic behaviour of the measurements and tap positions is developed. It is based on the simultaneous state and tap position estimation method augmented by measurement prefiltering based bad data detection and incorporation of a tap position dynamics model into the estimation algorithm. Increased bad data identification reliability and the robustness of the estimates to the measurement noise is obtained. The performance of the algorithm has been examined using the IEEE 30 and 118-node systems.
Keywords :
"Signal detection","State estimation","Power system dynamics","Power system modeling","Power system measurements","Power system reliability","Noise measurement","Data processing","Redundancy","Position measurement"