DocumentCode :
3804451
Title :
Other Factors Contributing to the Core Loss Performance of Power and Distribution Transformers
Author :
E. TeNyenhuis;R. Girgis;G. Mechler
Author_Institution :
ABB Electrical Systems Technology Institute
Volume :
21
Issue :
7
fYear :
2001
Firstpage :
70
Lastpage :
70
Abstract :
This paper presents results of analytical and experimental studies that give insight into the nature and mechanism of the generation of localized losses in the core joints, losses caused by core stacking holes, and the increase of iron loss of the core material due to slitting. These three loss components alone have been found to contribute about 3-4% to the total no-load loss of a large power transformer and as much as 10% in a small distribution transformer. The results show how the magnitude of these loss components varies with operating flux density, core material, excitation frequency, and geometrical parameters of the core.
Keywords :
"Core loss","Performance loss","Artificial neural networks","Power transformers","Transformer cores","Wavelet transforms","Frequency","Circuit faults","Magnetic flux","Surges"
Journal_Title :
IEEE Power Engineering Review
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.2001.4311487
Filename :
4311487
Link To Document :
بازگشت