DocumentCode :
3810768
Title :
A new approach to the arcing faults detection for fast autoreclosure in transmission systems
Author :
M.B. Djuric;V.V. Terzija
Author_Institution :
Dept. of Electr. Eng., Belgrade Univ., Serbia
Volume :
10
Issue :
4
fYear :
1995
Firstpage :
1793
Lastpage :
1798
Abstract :
To avoid automatic reclosing on permanent faults, a new numerical algorithm for power transmission network arcing faults detection has been developed. Some important features of a long arc in air are investigated and used as a basis in the algorithm design. The fact that the nonlinear arc behavior influences other voltages and currents distorting them, offered an opportunity to detect the arc by measuring and processing the transmission line terminal voltage and current. A series of simulation studies have shown that the algorithm can be used as an effective tool for arcing faults detection.
Keywords :
"Fault detection","Electrical fault detection","Voltage","Power transmission","Algorithm design and analysis","Nonlinear distortion","Distortion measurement","Current measurement","Transmission line measurements","Power transmission lines"
Journal_Title :
IEEE Transactions on Power Delivery
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.473378
Filename :
473378
Link To Document :
بازگشت