DocumentCode
3812468
Title
Effect of Neutral Path Power Losses on the Apparent Power Definitions: A Preliminary Study
Author
Slobodan Pajic;Alexander E. Emanuel
Author_Institution
Worcester Polytech. Inst., Worcester, MA
Volume
24
Issue
2
fYear
2009
Firstpage
517
Lastpage
523
Abstract
This paper presents the theoretical background needed to understand the effect of the parameters that affect the ratio rho between the equivalent neutral path resistance and line resistance of a transposed three-phase line. The ratio rho has a significant impact on the value of the apparent power as defined in IEEE Std. 1459. The ratio rho, however, depends on the topology of the power network as well as the type and size of the loads supplied by the feeder on which the apparent power is measured. It was found that for a wide range of conditions rho ap R 0/R +, where R 0, R + are the zero- and positive-sequence resistances of the line supplying the observed load.
Keywords
"Power measurement","Network topology","Electrical resistance measurement","Size measurement","Power quality","Geometry","Costs","Temperature","Voltage"
Journal_Title
IEEE Transactions on Power Delivery
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2009.2014481