DocumentCode :
384028
Title :
A live-line measurement method to parameters of high voltage cable lines with mutual inductance based on GPS
Author :
Zhijian, Hu ; Chengxue, Zhang ; Yunping, Chen
Author_Institution :
Sch. of Electr. Eng., Wuhan Univ., Hubei, China
Volume :
2
fYear :
2002
fDate :
2002
Firstpage :
969
Abstract :
The theoretical calculation method with formulae and the conventional measurement method of zero-sequence self-and mutual-impedance of high voltage cable lines are reviewed. Then the principles and mathematical models of zero-sequence parameter live-line measurement method of cable lines with mutual inductance based on GPS (Global Positioning System) technology are presented together with key techniques, hardware structure and software algorithm of the measurement system. Finally, field measurement results with the three different methods are given. Theoretical analysis and field measurement results prove that this new live-line method proposed in the paper is correct, effective and efficient.
Keywords :
Global Positioning System; electric impedance; inductance; power cables; power overhead lines; power system measurement; GPS; Global Positioning System; high voltage cable lines; live-line measurement method; mutual inductance; zero-sequence mutual-impedance; zero-sequence self-impedance; Current measurement; Global Positioning System; Inductance measurement; Power cables; Power system protection; Power system relaying; Power system reliability; Power transmission lines; Transmission line measurements; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN :
0-7803-7459-2
Type :
conf
DOI :
10.1109/ICPST.2002.1047543
Filename :
1047543
Link To Document :
بازگشت