    Analysis of the influence of specific humidity on positive streamer predischarges considering h/δ greater than 15 g/m3

  • Author

    Calva, P.A. ; Cabrera, G.P. ; Mejía, J. ; Portillo, A.R. ; Pérez, E. ; Espino, F.P. ; Fonseca, J.

  • Author_Institution
    ESIME Zacatenco, Instituto Politecnico Nacional, Mexico City, Mexico
  • fYear
    2002
  • fDate
    2002
  • Firstpage
    770
  • Lastpage
    773
  • Abstract
    The humidity correction factors specified by IEC Publication 60-1 (1989) and IEEE Std.-4 (1995) for impulse voltages are restricted to 1≤h/δ<15. However, values of h/δ≥15 g/m3 in many regions of the world are present. The IEC-60 and the IEEE Std.-4 procedures are based on the macroscopic observation that the atmospheric correction factors are larger when the discharge is governed mainly by positive streamers; while they tend to be lower when leaders or negative streamers are present. A better atmospheric correction factor implies to study the influence of atmospheric parameters on each discharge mechanism of the breakdown process. In this paper for standard lightning impulse voltages an analysis of the influence of absolute humidity divided by relative air density (h/δ) greater than 15 g/m3 on the positive streamer predischarges is reported.
  • Keywords
    flashover; humidity; surface discharges; artificial climatic chamber; humidity correction factors; impulse voltages; positive streamer predischarges; relative air density; specific humidity; Electric breakdown; Electrodes; Flashover; Humidity; IEC standards; Insulation; Lightning; Temperature; Testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena, 2002 Annual Report Conference on
  • Print_ISBN
    0-7803-7502-5
  • Type

    conf

  • DOI
    10.1109/CEIDP.2002.1048909
  • Filename
    1048909