• DocumentCode
    3860813
  • Title

    Topology error identification using normalized Lagrange multipliers

  • Author

    K.A. Clements;A.S. Costa

  • Author_Institution
    Worcester Polytech. Inst., MA, USA
  • Volume
    13
  • Issue
    2
  • fYear
    1998
  • Firstpage
    347
  • Lastpage
    353
  • Abstract
    This paper introduces a method for topology error identification based on the use of normalized Lagrange multipliers. The proposed methodology models circuit breakers as network switching branches whose statuses are treated as operational constraints in the state estimation problem. The corresponding Lagrange multipliers are then normalized and used as a tool for topology error identification, in the same fashion as measurement normalized residuals are conventionally employed for analog bad data processing. Results of tests performed with the proposed algorithm for different types of topology errors are reported.
  • Keywords
    "Lagrangian functions","Network topology","Circuit breakers","Circuit topology","State estimation","Switches","Power system modeling","Power system analysis computing","Power system economics","Switching circuits"
  • Journal_Title
    IEEE Transactions on Power Systems
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/59.667350
  • Filename
    667350