DocumentCode :
3861076
Title :
Time domain solution of fault distance estimation and arcing faults detection on overhead lines
Author :
M.B. Djuric;Z.M. Radojevic;V.V. Terzija
Author_Institution :
Fac. of Electr. Eng., Belgrade Univ., Serbia
Volume :
14
Issue :
1
fYear :
1999
Firstpage :
60
Lastpage :
67
Abstract :
In this paper a new numerical algorithm for arcing faults detection and fault distance estimation is presented. The solution is given in the time domain. It is based on the line terminal voltages and currents processing. A simple new mathematical model of arc voltage is introduced in the estimation. Thereby, the more accurate approach to fault location is derived, particularly for the close-in faults. The new algorithm can be utilized for blocking the automatic reclosing. The unknown model parameters, including the line resistance and inductance, fault resistance and arc voltage amplitude, are estimated by using the least error squares method. The new algorithm is successfully tested through computer simulation and laboratory tests.
Keywords :
"Voltage","Testing","Fault detection","Mathematical model","Fault location","Inductance","Amplitude estimation","Computer errors","Computer simulation","Laboratories"