• DocumentCode
    3861681
  • Title

    Modeling and control of a synchronous generator with an active DC load

  • Author

    I. Jadric;D. Borojevic;M. Jadric

  • Author_Institution
    York Int. Corp., PA, USA
  • Volume
    15
  • Issue
    2
  • fYear
    2000
  • Firstpage
    303
  • Lastpage
    311
  • Abstract
    The design and analysis of a system consisting of a variable-speed synchronous generator that supplies an active DC load (inverter) through a three-phase diode rectifier requires adequate modeling in both time- and frequency-domains. As an example, the system´s control-loops are difficult to design without an accurate small-signal model; at the same time, the system protection design requires large-signal transient modeling. A particularity of the described system is strong nonideal operation of the diode rectifier, a consequence of the large value of the generator´s synchronous impedance. This nonideal behavior influences both steady-state and transient performance. This paper presents an average model of the system that accounts, in a detailed manner for the dynamics of the power source and the load, and for the effects of the nonideal operation of the diode rectifier. The model is nonlinear, but time-continuous, and can be used for large- and small-signal analysis. The developed model was verified on a 105 kW generator-set with inverter output, whose DC-link voltage control-loop design was successfully carried out based on the average model. It is shown that a high bandwidth is needed for this control-loop in order to achieve the proper impedance matching between the power source and the active electronic load.
  • Keywords
    "Synchronous generators","Diodes","Rectifiers","Power system modeling","Inverters","Frequency","Control system synthesis","Protection","Impedance","Steady-state"
  • Journal_Title
    IEEE Transactions on Power Electronics
  • Publisher
    ieee
  • ISSN
    0885-8993
  • Type

    jour

  • DOI
    10.1109/63.838103
  • Filename
    838103