The production of magnetic fields from single pole encapsulated switchgear installations is significantly determined by the propagation of sheath currents on the encapsulation. This paper outlines investigations concerning the creation of sheath currents, concerning their distribution on the encapsulation as well as their influence on the resulting magnetic fields caused by the switchgear. Numerical simulations on the basis of the method of moments were performed which take into account the induction of sheath currents and which were used to calculate magnetic field distributions in the vicinity of single-pole encapsulated switchgear. The numerical data were compared with results obtained by measurements at real switchgear installations.
Keywords :
current distribution; encapsulation; magnetic fields; numerical analysis; switchgear; magnetic fields production; sheath currents creation; sheath currents distribution; shielding properties; single-pole encapsulated switchgear installations; Automation; Bars; Conductors; Electromagnetic compatibility; Encapsulation; Magnetic field measurement; Magnetic fields; Production; Substations; Switchgear;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility, 2002 3rd International Symposium on
Print_ISBN :
0-7803-7277-8
Type :
conf
DOI :
10.1109/ELMAGC.2002.1177399
Filename :
1177399
Link To Document :
بازگشت