• DocumentCode
    389886
  • Title

    The theory and application of differential protection based on instantaneous values

  • Author

    Yufeng, Hu ; Deshu, Chen ; Xianggen, Yin ; Zhe, Zhang ; Yanxia, Chen

  • Volume
    1
  • fYear
    2002
  • fDate
    6-10 Oct. 2002
  • Firstpage
    130
  • Abstract
    This paper introduces the new current differential protection based on instantaneous values. Firstly, some theory problems about the novel method are discussed, the operation equation of the protection is presented and its reliability effected by data window is analyzed. The main result obtained is that the width of the data window should be greater than π/2. Then, the paper discusses the special operation character of the novel protection that is called fuzzy zone. Some corresponding conclusions about the above discussion are given. Finally, the paper presents some practical application of the novel protection.
  • Keywords
    magnetisation; power system transients; power transformer protection; surge protection; current differential protection; current transformer saturation; data window; fuzzy zone; magnetizing inrush current; protection reliability; Circuit faults; Current transformers; Data analysis; Differential equations; Fault currents; Frequency; Protection; Protective relaying; Reliability theory; Saturation magnetization;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
  • Print_ISBN
    0-7803-7525-4
  • Type

    conf

  • DOI
    10.1109/TDC.2002.1178272
  • Filename