DocumentCode
389886
Title
The theory and application of differential protection based on instantaneous values
Author
Yufeng, Hu ; Deshu, Chen ; Xianggen, Yin ; Zhe, Zhang ; Yanxia, Chen
Volume
1
fYear
2002
fDate
6-10 Oct. 2002
Firstpage
130
Abstract
This paper introduces the new current differential protection based on instantaneous values. Firstly, some theory problems about the novel method are discussed, the operation equation of the protection is presented and its reliability effected by data window is analyzed. The main result obtained is that the width of the data window should be greater than π/2. Then, the paper discusses the special operation character of the novel protection that is called fuzzy zone. Some corresponding conclusions about the above discussion are given. Finally, the paper presents some practical application of the novel protection.
Keywords
magnetisation; power system transients; power transformer protection; surge protection; current differential protection; current transformer saturation; data window; fuzzy zone; magnetizing inrush current; protection reliability; Circuit faults; Current transformers; Data analysis; Differential equations; Fault currents; Frequency; Protection; Protective relaying; Reliability theory; Saturation magnetization;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN
0-7803-7525-4
Type
conf
DOI
10.1109/TDC.2002.1178272
Filename
1178272
Link To Document