Title :
PV hybrid system and battery test results from Grasmere Idaho
Author :
Hund, Thomas D. ; Gates, Scott
Author_Institution :
Sandia Nat. Labs., Albuquerque, NM, USA
Abstract :
In large PV hybrid power systems battery management is critical due to the continuous operation of the power system, the limited power available for temperature control in the battery room, and the high cost of maintenance. A new C&D CPV deep-cycle low antimony vented battery has been tested in the laboratory and at the Grasmere Idaho PV hybrid power system to evaluate battery capacity, charge requirements, temperature, and cost. Laboratory cycle tests on the battery were used to evaluate appropriate charge control for PV hybrid applications and battery field performance was verified after 2.5-years of operation at Grasmere Idaho. Test results demonstrated that with proper system and battery design using appropriate charge control, the battery will operate reliably with minimal maintenance under the continuous operational requirements of a large PV hybrid power system.
Keywords :
battery management systems; diesel-electric generators; hybrid power systems; invertors; photovoltaic power systems; secondary cells; 100 kW; 210 kW; 30 to 90 kW; Grasmere Idaho; PV hybrid system; battery capacity; battery maintenance; battery management; battery room; battery temperature; battery test results; charge control; charge requirements; continuous operation; deep-cycle low antimony vented battery; diesel generators; inverter; maintenance; Battery management systems; Costs; Energy management; Hybrid power systems; Laboratories; Power system control; Power system management; Power system reliability; Power systems; System testing;
Conference_Titel :
Photovoltaic Specialists Conference, 2002. Conference Record of the Twenty-Ninth IEEE
Print_ISBN :
0-7803-7471-1
DOI :
10.1109/PVSC.2002.1190876