Title : 
Speeding-up dynamic response of active power conditioners
         
        
            Author : 
Silva, Luiz Eduardo Borges da ; de Lacerda de Oliveira, Levy Ely ; Silva, Valberto Ferreira da ; Torres, Germano Lambert ; Bonaldi, Erik Leandro ; Rossi, Ronaldo
         
        
            Author_Institution : 
Taubate Univ., Brazil
         
        
        
        
        
        
            Abstract : 
The id-iq control method is one of the most widespread control methods for active power filters. Two improvements to this method are presented: the elimination of the PLL (phase locked loop) in active power filters for harmonic current compensation only and a strategy for achieving the best transient time. PLL elimination is an important simplification for reducing the computational effort in a digital implementation as well as for improving transient time. The achievement of the best transient time is essential for an efficient compensation of currents with time-varying harmonic content. The paper describes both improvements and presents simulations and experimental results.
         
        
            Keywords : 
active filters; dynamic response; moving average processes; phase locked loops; power harmonic filters; PLL; active power conditioners; active power filters; dynamic response; harmonic power compensation; id-iq control method; moving average technique; phase locked loops; time-varying harmonic content; Active filters; Computational modeling; Current supplies; Low pass filters; Phase locked loops; Power harmonic filters; Power system harmonics; Voltage control;
         
        
        
        
            Conference_Titel : 
Electrical and Computer Engineering, 2003. IEEE CCECE 2003. Canadian Conference on
         
        
        
            Print_ISBN : 
0-7803-7781-8
         
        
        
            DOI : 
10.1109/CCECE.2003.1226412