A new method to balance currents of the generator
Author
Ding, Hongfa ; Duan, Xianzhong
Author_Institution
Huazhong Univ. of Sci. & Technol., China
Volume
1
fYear
2003
fDate
4-7 May 2003
Firstpage
371
Abstract
In modern power systems, most generators use negative sequence current relays to detect the negative sequence current and, if necessary, alarm or trip the generators to protect them from the damage of it. However, tripping major generation facilities may create social, security, and economic problems. This paper presents a feasible method for negative sequence current reduction at the generator terminal through a special function single-phase active power filter (APF), which can be connected to system either at Y0 or Δ side of the transformer between the generator and the transmission lines. The control algorithm and digital simulation results of this method are also presented in this paper.
Keywords
active filters; electric current; electric generators; machine control; machine protection; power filters; active power filters; generator protection; negative sequence current relays; Active filters; Digital control; Power generation; Power generation economics; Power system economics; Power system protection; Power system relaying; Power system security; Power transmission lines; Protective relaying;