Title :
The evaluation of thermal aging for application of hybrid insulation system in oil filled pole mounted transformer
Author :
Lee, Byung-Sung ; Song, Il-Keun ; Kim, Ju-Yong ; Han, Sang-Ok
Author_Institution :
Korea Electr. Power Res. Inst., Daejeon, South Korea
Abstract :
Liquid-immersed pole transformers have utilized an insulation system consisting of natural cellulose-based materials and mineral oil for many years. If the transformers are installed with the abruptly changing load over limitation, its insulation materials are apt to unexpected aging with high temperature. Therefore we have been conscious of developing a transformer that is more thermally stable then conventional types. To measure temperature distribution in the winding of conventional and newly designed transformers, temperature sensors were installed for direct reading of oil and conductor temperatures at transformers. And we conducted accelerating aging test for these transformers. The measuring data had made use of the design to hybrid insulation system. Also we could find the possibility of this insulation system to apply in pole mounted transformers.
Keywords :
ageing; insulating materials; power transformers; temperature measurement; temperature sensors; thermal stability; transformer oil; accelerated aging test unit; hybrid insulation system; insulation materials; liquid immersed pole transformers; mineral oil; oil filled pole mounted transformer; temperature distribution; temperature sensors; thermal aging evaluation; thermal stability; Aging; Conducting materials; Dielectric liquids; Minerals; Oil insulation; Petroleum; Power transformer insulation; Temperature distribution; Temperature measurement; Temperature sensors;
Conference_Titel :
Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Technology Conference, 2003. Proceedings
Print_ISBN :
0-7803-7935-7
DOI :
10.1109/EICEMC.2003.1247953