Abstract :
Two different standardized trench layouts, containing, gas and water pipelines, telephone cables, 1-kV and 10kV-cables (LV and MV-cables), so-called multiple-supply service trenches, were analyzed with respect to their thermal loading. In principle, two different options were regarded, i.e. with currents in the cables according to VDE 0276 part 1000 and based on the current obtained for the maximal permissible temperature of the cable conductor as determined by the calculating program. The calculations according standard loading conditions resulted for realistic thermal soil conditions (λ = 1.5Km/W; ϑsoil = 15 C) in a maximal temperature of the water pipe of 20.1 C assuming a water temperature of 18 C. In case of the worst conditions i.e. λ = 1.5Km/W; ϑsoil = 15 C the maximal temperature for the water pipe will increase up to 21.5 C.
Keywords :
CAD; cable laying; design engineering; pipelines; LV cable; MV cable; cable conductor; cable loading; cable trench; gas pipeline; maximal permissible temperature; multiple-supply service trench; permissible current; thermal loading; thermal soil condition; water pipeline; Conductors; Design optimization; Pipelines; Power cables; Protection; Soil; Telephony; Temperature; Thermal loading; Water heating;
Conference_Titel :
EUROCON 2003. Computer as a Tool. The IEEE Region 8
Print_ISBN :
0-7803-7763-X
DOI :
10.1109/EURCON.2003.1247986