• DocumentCode
    400280
  • Title

    UPS with an electric-energy storage function using VRLA batteries

  • Author

    Kiyokawa, Ichiro ; Tsujikawa, Tomonobu ; Matsushima, Toshio ; Muroyama, Seiichi

  • Author_Institution
    NTT Facilities Inc., Tokyo, Japan
  • fYear
    2003
  • fDate
    23-23 Oct. 2003
  • Firstpage
    808
  • Lastpage
    813
  • Abstract
    A UPS with an energy storage function using long-cycle-life VRLA batteries has been developed. Combining the functions of UPS and energy storage is effective to enhance the cost- effectiveness of the UPS. New long-cycle-life VRLA batteries, with capacities of 1000 or 1500 Ah at 2 V, have been developed for the UPS. A cycle life of 3000 or more cycles was estimated from our cycle test. The UPS has been installed in a telecommunications building for field testing. This paper describes the system configuration, electrical characteristics of the UPS and its components, and result of our field test.
  • Keywords
    energy storage; lead acid batteries; telecommunication power supplies; uninterruptible power supplies; UPS; VRLA batteries; cycle life; cycle test; electric-energy storage function; field testing; telecommunications building; Batteries; Circuits; Condition monitoring; Energy storage; Maintenance; Power supplies; Power system reliability; Remote monitoring; Testing; Uninterruptible power systems;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Telecommunications Energy Conference, 2003. INTELEC '03. The 25th International
  • Conference_Location
    Yokohama, Japan
  • Print_ISBN
    4-88552-196-3
  • Type

    conf

  • Filename
    1252209