    Application of controlled switching to 500 kV shunt reactor current interruption

  • Author

    Kobayashi, Takehiko ; Tsukao, Shigeyuki ; Ohno, Lchiro ; Koshizuka, Tadashi ; Nishiwaki, Susumu ; Miyake, Nobuyuki ; Matsushita, Kozo ; Saida, Toshiyuki

  • Volume
    3
  • fYear
    2003
  • fDate
    13-17 July 2003
  • Firstpage
    1930
  • Abstract
    Summary form only given. To suppress re-ignition overvoltages caused when a 500 kV shunt reactor current is interrupted by a 550 kV one-break circuit breaker, a study was carried out on controlled switching. Using a full-scale test circuit, reactor current interruption tests were carried out to obtain the relation between opening phase angle and the generation of re-ignition. The results showed that even with the dispersion of circuit breaker operations taken into account, there were contact separation points free from high re-ignition overvoltages. It was also proved that no voltage escalations were caused by re-ignition and high-frequency arc extinction, and that the overvoltages due to current chopping were at safe level in terms of equipment insulation.
  • Keywords
    circuit breakers; overvoltage protection; power system faults; power system protection; reactors (electric); switching substations; 500 kV; 550 kV; controlled switching; current chopping; equipment insulation; high-frequency arc extinction; one-break circuit breaker; opening phase angle; reactor current interruption tests; reignition overvoltages; reignition overvoltages suppress; shunt reactor current interruption; substation; test circuit; voltage escalations; Circuit breakers; Circuit testing; Ignition; Inductors; Insulation; Shunt (electrical); Substations; Surges; Switching circuits; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society General Meeting, 2003, IEEE
  • Print_ISBN
    0-7803-7989-6
  • Type

    conf

  • DOI
    10.1109/PES.2003.1267459
  • Filename
    1267459