• DocumentCode
    420009
  • Title

    Improving the energetic efficiency of distribution busbars

  • Author

    Gonnet, J.-P. ; Guichon, J.-M. ; Clavel, E. ; Roudet, J. ; Mazauric, V.

  • Author_Institution
    Schneider Electr. Corp. Res. & Dev., Grenoble, France
  • Volume
    2
  • fYear
    2003
  • fDate
    7-12 Sept. 2003
  • Firstpage
    633
  • Abstract
    We present a study on the energetic efficiency of power distribution busbars. This kind of pipe-oriented conductors is highly influenced by induced effects. Indeed, proximity and skin effects cause non-uniform current repartitions, which lead to important Joule losses, i.e. wasted energy. Using the partial electrical equivalent circuit method, which does not require a meshing of air, we are able to evaluate the impact of these effects. We then propose a method to reduce the impact of skin effect by modifying the design of the cross-section of bars. This allows an improvement of busbars efficiency which can be reported on different categories of savings, including environmental criteria, allowing busbars to join a sustainable development process.
  • Keywords
    busbars; equivalent circuits; power distribution; sustainable development; energetic efficiency; environmental factors; nonuniform current repartitions; partial electrical equivalent circuit method; pipe-oriented conductors; power distribution busbars; skin effect; wasted energy; Bars; Conducting materials; Costs; Insulation; Power distribution; Production; Skin effect; Substations; Temperature; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2003 IEEE PES
  • Print_ISBN
    0-7803-8110-6
  • Type

    conf

  • DOI
    10.1109/TDC.2003.1335350
  • Filename
    1335350