Title :
Research on the compensation mode and new principal-auxiliary arc-suppression coil in the resonant grounded system
Author :
Hongbo, Lian ; Yihan, Yang ; Xukai, Zhu ; Weipu, Tan
Author_Institution :
North China Electr. Power Univ., Beijing, China
Abstract :
The selection of compensation mode and the arc-suppression coil is the main problem in the operation of resonant grounded systems. This paper proposes a new compensation mode that is a combination of presetting mode and following-setting mode, which can do great help to the self-extinction of the instantaneous grounded arcs. In this mode, the arc-suppression coil is preset to some place that is about 15% over-compensation when the system is healthy, and the arc-suppression coil is quickly following-set to the full compensation point when the single-phase-to-ground fault occurs. To demonstrate this, a new principal-auxiliary arc-suppression coil is designed. The auxiliary arc-suppression coil composes of N fine-tuning coils, switched by N thyristors. The inductance of them adopts binary-weave system, which form 2N compensation values. The results of the 10 kV physical simulating experiments and simulation with EMTP/ATP verify the reliability and validity of this compensation mode and the new principal-auxiliary arc-suppression coil proposed in this paper.
Keywords :
EMTP; arcs (electric); coils; earthing; power system faults; power system protection; 10 kV; EMTP/ATP; MV power system; binary-weave system; compensation mode; fine-tuning coils; following-setting mode; instantaneous grounded arc self-extinction; presetting mode; principal-auxiliary arc-suppression coil; resonant grounded system; single-phase-to-ground fault; thyristors; Coils; EMTP; Electricity supply industry; Fault currents; Inductance; Power system reliability; Power system security; Resonance; Thyristors; Voltage;
Conference_Titel :
Power System Technology, 2004. PowerCon 2004. 2004 International Conference on
Print_ISBN :
0-7803-8610-8
DOI :
10.1109/ICPST.2004.1460087