• DocumentCode
    44570
  • Title

    Transmission-Line Protection: A Directional Comparison Scheme Using the Average of Superimposed Components

  • Author

    Hashemi, S.M. ; Hagh, Mehrdad Tarafdar ; Seyedi, Heresh

  • Author_Institution
    Faculty of Electrical and Computer Engineering, University of Tabriz, Tabriz, Iran
  • Volume
    28
  • Issue
    2
  • fYear
    2013
  • fDate
    Apr-13
  • Firstpage
    955
  • Lastpage
    964
  • Abstract
    In this paper, a new protection scheme for transmission lines is presented. The method has some advantages in comparison with conventional line protection schemes. Faster fault detection and instantaneous coverage of almost 100% of the line are the main advantages of the new method. A full-cycle averaging window is used for fault detection. While the power system is in normal operation conditions, this average is approximately equal to zero. As soon as the faulty signals enter the window, the average is changed to a nonzero value. It is shown that the product of this average value for voltage and current of the faulty phase, in a specific time interval after fault inception, is negative for the forward faults and positive for the reverse faults. The fault is detected by communication between the local and the remote relays. Simulation and experimental results show the efficiency of the proposed method in fast detection of line faults in less than a half cycle.
  • Keywords
    Circuit faults; Fault detection; Power transmission lines; Relays; Steady-state; Transient analysis; Directional comparison; protection; relaying; superimposed component; transmission line;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2012.2226609
  • Filename
    6450136