• DocumentCode
    45017
  • Title

    Application of Wavelet Transform to Obtain the Frequency Response of a Transformer From Transient Signals—Part II: Practical Assessment and Validation

  • Author

    Gomez-Luna, E. ; Aponte Mayor, G. ; Pleite Guerra, Jorge

  • Author_Institution
    Univ. del Valle, Cali, Colombia
  • Volume
    29
  • Issue
    5
  • fYear
    2014
  • fDate
    Oct. 2014
  • Firstpage
    2231
  • Lastpage
    2238
  • Abstract
    This paper presents a practical assessment and validation for the new proposed approach based on the continuous wavelet transform (CWT) to obtain the frequency response from online transient signals for an actual transformer. Apart from the mathematical procedure, an electronic system was also designed and implemented in order to inject superimposed controlled pulses to the power system (50/60 Hz) wave. The results show improved performance of the wavelet transform compared to the Fourier transform, for transient signal analysis to be applied on a nonintrusive transformer monitoring approach. Particularly, this new approach enables overcoming some problems related to the signal filtering and the signal processing in an online frequency-response analysis transformer diagnosis. This paper is presented in three parts. Part I showed the main theoretical basis of this approach. The current Part II shows a practical assessment based on tests performed in a three-phase transformer of 1150/345 V-5 kVA and in a single-phase transformer of 13200/240 V-15 kVA. Part III shows the performance of this new approach on transformers being diagnosed under real conditions.
  • Keywords
    filtering theory; frequency response; power system transients; power transformers; wavelet transforms; CWT; apparent power 15 kVA; apparent power 5 kVA; continuous wavelet transform; electronic system; nonintrusive transformer monitoring approach; online frequency-response analysis; online transient signals; power system wave; signal filtering; signal processing; single-phase transformer; three-phase transformer diagnosis; transient signal analysis; voltage 1150 V to 345 V; voltage 13200 V to 240 V; Continuous wavelet transforms; Frequency measurement; Multiresolution analysis; Transient analysis; Windings; Continuous wavelet transform (CWT); frequency response; online monitoring; power system transients; transformers;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2295377
  • Filename
    6698401