DocumentCode
45493
Title
Critical clearing time estimation using synchrophasor data-based equivalent dynamic model
Author
Paul, Avishek ; Senroy, Nilanjan
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol. Delhi, New Delhi, India
Volume
9
Issue
7
fYear
2015
fDate
4 30 2015
Firstpage
609
Lastpage
614
Abstract
A critical aspect of online dynamic security assessment is the ranking of probable contingencies based on the critical clearing time. Ordinarily critical clearing time involves simulation of contingencies requiring extensive computational resources and updated network data. This study proposes to use reduced order equivalents of the network around a critical tie line, to estimate the critical clearing time. It is proposed to derive the reduced order model from synchrophasor data in real time, so as to replicate the most updated system dynamics. The stability margins in the reduced order model and the original detailed model are correlated using a transient energy function that considers the kinetic and potential energy gained by any system during a fault. It is shown that it is possible to arrive at a relatively accurate estimate of the critical clearing time of a contingency in the detailed model, using the equivalent model obtained using synchrophasors data.
Keywords
phasor measurement; power system security; reduced order systems; critical clearing time estimation; kinetic energy; online dynamic security assessment; potential energy; reduced order equivalents; reduced order model; stability margins; synchrophasor data-based equivalent dynamic model; transient energy function;
fLanguage
English
Journal_Title
Generation, Transmission & Distribution, IET
Publisher
iet
ISSN
1751-8687
Type
jour
DOI
10.1049/iet-gtd.2014.0519
Filename
7095696
Link To Document