Title :
Discharge Properties in Low Vacuum and Vacuum Monitoring Method for Vacuum Circuit Breakers
Author :
Saito, Hitoshi ; Matsui, Yoshihiko ; Sakaki, Masayuki
Author_Institution :
Medium Voltage Switchgear Dev. Dept., Japan AE Power Syst. Corp., Numazu
Abstract :
One of the causes leading to the low performance of vacuum interrupters (VIs) is a slow leak. If no measures are taken, this phenomenon cannot be detected and the VI will develop serious faults. Therefore, an effective monitoring technique is essential. We experimentally investigated the discharge properties in the low vacuum region of a VI. We measured the signal intensity of the discharge signal caused by the discharge occurring inside a model VI whose degree of vacuum could be varied. Pulse pattern and pulse waveforms were also measured in various pressures. To understand the pattern generating mechanism, we simulated these discharge patterns. Two noise reduction method using timer and frequency filter was examined. Finally, we introduce on-line vacuum-monitoring device with an alarm to warn of the deterioration of the vacuum degree of VIs
Keywords :
partial discharge measurement; vacuum circuit breakers; vacuum interrupters; discharge patterns; discharge properties; discharge signal; frequency filter; online vacuum-monitoring device; pattern generating mechanism; pulse pattern; pulse waveforms; signal intensity; vacuum circuit breakers; vacuum degree; vacuum interrupters; Circuit breakers; Circuit faults; Electrical fault detection; Fault detection; Filters; Frequency; Interrupters; Monitoring; Noise reduction; Pulse measurements;
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2006. ISDEIV '06. International Symposium on
Conference_Location :
Matsue
Print_ISBN :
1-4244-0191-7
Electronic_ISBN :
1093-2941
DOI :
10.1109/DEIV.2006.357262