DocumentCode :
462881
Title :
Interaction of a Vacuum Arc with an SF6 Arc in a Hybrid Circuit Breaker during High-Current Interruption
Author :
Smeets, R.P.P. ; Kertesz, V. ; Dufournet, Denis ; Penache, D. ; Schlaug, M.
Author_Institution :
KEMA T&D Testing Services, Arnhem
Volume :
1
fYear :
2006
fDate :
25-29 Sept. 2006
Firstpage :
220
Lastpage :
223
Abstract :
A hybrid circuit breaker consists of a series connected vacuum- and SF6 interrupter. The vacuum interrupter has the function to withstand very steep rising transient recovery voltages, whereas the SF6 interrupter is stressed with the peak of this voltage. Full scale tests are described of a 145 kV prototype, subjected to short-line faults based on 63 kA. During these tests, current through the breaker and voltages across both interrupters were monitored with a high-resolution measurement system. It is shown that the principal idea works correctly. From measured results, it is demonstrated that the interaction between the two arcs of completely different physical nature has a positive effect on the interruption: immediately before current zero the SF6 arc assists the vacuum arc to interrupt, whereas after current zero the vacuum arc assists the SF6 arc in the withstand of the recovery voltage
Keywords :
circuit-breaking arcs; vacuum interrupters; 145 kV; 63 kA; SF6 arc; current zero; high-current interruption; high-resolution measurement system; hybrid circuit breaker; short-line faults; vacuum arc; very steep rising transient recovery voltages; Circuit breakers; Circuit faults; Circuit testing; Current measurement; Interrupters; Prototypes; Sulfur hexafluoride; System testing; Vacuum arcs; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2006. ISDEIV '06. International Symposium on
Conference_Location :
Matsue
ISSN :
1093-2941
Print_ISBN :
1-4244-0191-7
Electronic_ISBN :
1093-2941
Type :
conf
DOI :
10.1109/DEIV.2006.357272
Filename :
4194852
Link To Document :
بازگشت